Warehouse or factory? NCC building classes and fire rules explained

Design · Updated · 7 min read

Short answer

Under the National Construction Code a warehouse used for storage or wholesale display is Class 7b, a building where goods are produced, assembled, repaired, packed or cleaned is Class 8, and an office is Class 5. A building can contain several classes and must meet the requirements of each, with the more stringent one applying where they conflict (NCC 2022, A6G12). Queensland applies NCC 2022 until NCC 2025 is adopted on 1 May 2027.

Concept visualisation of a clear-span warehouse interior
A clear-span warehouse interiorConcept image

The classes that matter for industrial buildings

NCC 2022 Volume One building classes relevant to industrial projects (A6G6–A6G11)
ClassUseExample
5Office for professional or commercial purposesAttached office
7aCarparkCovered car parking
7bStorage, or display of goods or produce for wholesaleWarehouse, storage building
8Process building: goods produced, assembled, altered, repaired, packed, finished or cleaned; laboratoriesFactory, mechanic's workshop
10aNon-habitable buildingPrivate garage, carport, shed

A minor use of less than 10% of a storey's floor area can take the classification of the rest of that storey, except for laboratories and some other uses (A6G1).

Fire compartment limits

Maximum fire compartment size, Class 7 and 8 buildings (NCC 2022 Table C3D3)
Type of constructionMax floor areaMax volume
Type A5,000 m²30,000 m³
Type B3,500 m²21,000 m³
Type C2,000 m²12,000 m³

Larger buildings can use the large isolated building provisions (C3D4). Up to 18,000 m² and 108,000 m³, a Class 7 or 8 building of no more than two storeys with at least 18 m of open space around it can exceed the table limits; alternatively the building is sprinklered with perimeter vehicle access. Above those sizes, sprinklers and perimeter access are required. Perimeter access must be at least 6 m wide with its far edge no more than 18 m from the building (C3D5).

When sprinklers are triggered

  • Any part of the building with an effective height over 25 m (E1D5).
  • Large isolated buildings using the sprinkler route in C3D4.
  • Occupancies of excessive hazard over 2,000 m² or 12,000 m³, including storage of combustible goods with an aggregate volume over 1,000 m³ stored higher than 4 m, such as goods in cartons (E1D13).

Other provisions that shape the layout

  • Fire hydrants are required where total floor area exceeds 500 m² and a fire station with suitable equipment is within 50 km (E1D2).
  • Travel distance to an exit in Class 5 to 9 buildings: no point more than 20 m from an exit or a point with a choice of two exits, and no more than 40 m to one of them (D2D5).
  • Air-conditioned Class 5, 7b and 8 spaces are subject to an energy-use limit under Section J (J1P1).

Clause references are to NCC 2022 Volume One. Your certifier and fire engineer confirm how they apply to your building.

Tell us what the building has to do.

Send the lot address, the rough size and what the building is for. We check the zoning and approval pathway, suggest the structure that suits and come back with a budget range.

Monday to Friday, 8 am to 5 pm (AEST). Brisbane office visits by appointment.

Start your project quote

Step 1/3

  1. 01 Project
  2. 02 Details
  3. 03 Contact

Prefer to talk? Call 07 2142 1772

Call our teamRequest a quote